Air quality and productivity at work: what the research supports and what it does not

Chamber experiments, call-center data and a 12-month office study give mixed results on air quality and productivity. What each measured, where they disagree and what no study settles.

A line chart with scattered points above and below a flat line, labeled study by study, beside a desk icon

The research on air quality and productivity supports a few narrow findings and no general rule. Some controlled experiments found lower scores on decision-making tests at higher CO2 or lower ventilation. Others with similar designs found nothing, and the two studies of real work described below report associations that are weak, limited to some measures or inconsistent. ASHRAE's position document on indoor CO2 (approved 12 February 2025) calls the evidence for direct effects of CO2 on work performance at commonly observed concentrations inconsistent and says it does not currently justify changes to ventilation and indoor air quality standards.

What studies of air quality and productivity measure

Most studies measure productivity indirectly. Researchers use stand-ins: a computer simulation of running a business (the Strategic Management Simulation, scored on nine decision-making scales), typing speed, addition, proofreading, call handling time, or short reaction tests such as the Stroop color-word test. A gain on a test is not a measured gain in output. ASHRAE's position document notes that occupants are never exposed to pure CO2, and that raised CO2 in real rooms may mark inadequate ventilation, where other contaminants also build up. Experiments that add pure CO2 separate the two but are less like a real room.

Studies that found effects

Satish and colleagues (Environmental Health Perspectives, 2012) put 22 people, mostly university students, in a chamber for three 2.5-hour sessions on one day at about 600, 1,000 and 2,500 ppm. Pure CO2 was added to the supply air while ventilation and temperature were held constant, and neither participants nor the test administrator knew the level. The abstract reports moderate, statistically significant declines in six of nine decision-making scales at 1,000 ppm compared with 600 ppm, and large declines in seven scales at 2,500 ppm. The authors say generalizing from college students is uncertain and replication is needed, and that the 2,500 ppm effects were so large for some metrics as to "almost defy credibility."

Allen and colleagues (Environmental Health Perspectives, 2016) followed 24 professionals through six workdays in a controlled office lab, using the same simulation. Each day had a different mix of ventilation, CO2 and volatile organic compounds (VOCs) in a fixed order, participants were blinded, and each condition ran on one day except "Green+", which ran twice. Against a "Conventional" day (about 920 to 970 ppm CO2, 20 cfm of outdoor air per person, total VOCs of roughly 500 to 670 micrograms per cubic meter), scores were 61% higher on a low-VOC "Green" day and 101% higher on the two Green+ days with double the outdoor air (40 cfm per person, CO2 about 490 to 610 ppm). With the same 40 cfm but CO2 raised to about 1,400 ppm, scores were 50% lower than on the Green+ days; a day at about 945 ppm scored 15% lower.

The authors note that effects could carry over from one day to the next, that ozone varied between conditions, and that results need confirming in real offices. The study was funded by a gift from United Technologies. In HPAC Engineering (13 February 2016), engineer Kenneth Elovitz noted that the moderate-CO2 day interrupts the pattern and that temperature related to scores as strongly as CO2.

Wargocki, Wyon and Fanger (Healthy Buildings 2000 proceedings) combined three experiments in test offices, each with 30 women aged 18 to 33 doing simulated office work for 4.5 hours. A 20-year-old carpet from a building with a history of sick building syndrome symptoms was present or removed, and the third experiment also varied outdoor air at 3, 10 or 30 L/s per person. In the combined analysis, better air quality improved typing speed (P = 0.0002), while addition (P = 0.056) and proofreading (P = 0.087) showed only trends. The authors estimate that performance rises about 1.9% for every doubling of ventilation at constant pollution load. They say it was a simulated office and that validation in real offices would be useful.

Studies with null or inconsistent results

Rodeheffer and colleagues (Aerospace Medicine and Human Performance, 2018) gave the same simulation to 36 submarine-qualified sailors, each randomly assigned to 600, 2,500 or 15,000 ppm. No significant difference appeared on any of the nine measures, and the authors wrote that they were "unable to replicate this effect in a submariner population."

Scully and colleagues (npj Microgravity, 2019) exposed 22 astronaut-like adults to 600, 1,200, 2,500 and 5,000 ppm for about 3 hours each, in a randomized, double-masked crossover. They report no clear dose-response pattern: most simulation measures and aggregate cognition scores were lower at 1,200 ppm than at 600 ppm, while at higher concentrations performance was similar to or above baseline. The authors say the results agree with neither Satish nor Rodeheffer, and that ventilation differed between the 600 ppm condition and the others, so accumulated VOCs and bioeffluents could have played a part.

Zhang and colleagues (Indoor Air, 2017) tested 25 participants in five conditions of 255 minutes. Pure CO2 added to reach 1,000 or 3,000 ppm had no significant effect on perceived air quality, symptoms or cognitive performance. At 3,000 ppm from bioeffluents, perceived air quality worsened, participants reported more headache, fatigue and sleepiness, and some tasks were done worse.

Flagner and colleagues (IZA Discussion Paper 17019, May 2024, a working paper that IZA says often represents preliminary work) kept 20 office workers in an air-tight respiration chamber for 8 hours at 900 and 3,000 ppm, with high ventilation and a filter holding VOCs low. After correcting for multiple tests they reported no significant effect on cognition or economic decisions. The one physiological result that survived correction was small: respiration rate during morning tests was about one breath per minute higher at 3,000 ppm. They note the small sample and two tested levels.

What studies of real work show

Federspiel and colleagues (Indoor Air, 2004) studied registered nurses working in a call center, randomizing the position of the outdoor air dampers. Indoor-minus-outdoor CO2 ranged from 13 to 611 ppm. Talk time was shortest at the highest ventilation rate, but the authors call the relationship not strong or monotonic, and wrap-up time showed no significant association with ventilation. Wrap-up was slower above 25.4 degrees C, during long shifts and when staffing was short.

Cedeño Laurent and colleagues (Environmental Research Letters, 2021) collected data from 302 office workers in 42 buildings in six countries over 12 months. A phone app prompted short Stroop and addition-subtraction tests while sensors near workstations logged CO2. Per interquartile increase in CO2 (315 ppm), Stroop response time was 0.85% slower and Stroop interference time 7.88% slower, while the association with addition throughput was not significant. The authors cite large variation between people relative to these effects, relatively low model fit, commercial-grade sensors, a convenience sample of buildings and too few readings above 1,200 ppm. The design is observational, which limits what it can say about cause. Funding included a gift from Carrier Global Corporation, which the authors say was not involved in study design, data collection or analysis.

What reviews of air quality and productivity conclude

Seppänen, Fisk and Lei-Gomez (Indoor Air, 2006) combined studies of ventilation rate and work performance from laboratories and real buildings. Almost all found that performance rose with ventilation. The typical gain was about 1 to 3% per 10 L/s per person, larger below 20 L/s per person and almost negligible above 45, and statistically significant up to 15 L/s per person at the 95% confidence level.

Wyon and Wargocki (ASHRAE Journal, March 2013, republished in the REHVA Journal) report that many field studies found larger negative effects than laboratory work predicted, possibly because paid laboratory subjects exert more effort. Which pollutants and mechanisms cause the effects remains open, they write. They give the size of the negative effects of the indoor environment on adult performance as up to 5% in the laboratory and up to 10% in the field.

How an owner can use this evidence

The research on air quality and productivity described above does not establish a CO2 limit or a ventilation rate as a productivity target, and the studies do not agree on whether CO2 itself has an effect at office levels. For where the 1,000 ppm figure comes from, see What is a good CO2 level in an office?, and for what to measure in an office, see Indoor air quality in offices, how to measure it.

This is practical judgment, not a published finding. Room-by-room readings of CO2, temperature and humidity show whether the rooms people work in get the ventilation they were designed for, and give a record to set against complaints. They do not measure productivity, and a change in a reading is not evidence of a change in work output.