What an office gets from air quality monitoring
Air quality monitoring in offices shows which rooms get too little air, backs up complaints, finds ventilation running in empty rooms and checks a change. What the evidence supports, and its limits.
Air quality monitoring in offices gives a facility team a record of CO2 in each room while people are in it, which indicates how much outdoor air the room gets and which a one-off test cannot show. The record has four uses: finding rooms that run short of air, answering comfort complaints with data, cutting ventilation in rooms that are empty, and checking whether a change worked. Monitoring does not clean the air by itself.
What air quality monitoring in offices records
In most offices the core reading is CO2. The UK Health and Safety Executive (HSE) says 1,000 ppm is equivalent to about 10 L/s per person, but calls CO2 measurements only a broad guide to ventilation that does not demonstrate safe levels. ASHRAE's Government Affairs Office issue brief on indoor CO2 (updated June 2026) says CO2 can be used to verify whether ventilation performance meets existing standards, and that readings far above expected ranges likely indicate the system is not functioning properly. The same brief says interpretation needs context such as the number and activity level of occupants compared to design capacity, that sensor accuracy, location and calibration are all critical, and that CO2 does not indicate the quality of indoor air as a whole.
Indoor air quality in offices, how to measure it covers which parameters to add to CO2, and Testing air quality in an office compares a one-off test with a continuous record.
Finding the rooms that get too little air
The case for measuring ventilation rests on research that links low rates to worse outcomes. Seppänen, Fisk and Mendell (Indoor Air, 1999) reviewed 20 studies with close to 30,000 subjects in non-residential, non-industrial buildings, mainly offices. Almost all of the studies found that ventilation rates below 10 L/s per person were associated with a statistically significant worsening in at least one health or perceived air quality outcome. Fisk, Mirer and Mendell (Indoor Air, 2009) combined published data and estimated that the relative prevalence of sick building syndrome symptoms in office workers rises about 23% (range 12% to 32%) when ventilation drops from 10 to 5 L/s per person, and falls about 29% (range 15% to 42%) when it rises from 10 to 25 L/s per person. The authors caution that symptom types, building features and outdoor air quality can make a given building differ from that average.
These are studies of ventilation rate. A CO2 log can indicate whether a room's rate is near that range, and it does not measure symptoms. What the research supports on performance is covered in Air quality and productivity at work: what the research supports and what it does not.
CO2 can also differ within a single room. Berkeley Lab (LBNL-3279E, 2010) analyzed CO2 in occupied meeting rooms over 30 to 90 minute periods and found that concentrations at different wall-mounted sample points sometimes varied by more than 200 ppm. A single point can mislead for one room, and a floor reading blends many rooms, as covered in Why one CO2 sensor per floor misses the problem rooms. A simulation study points the other way. Rackes, Ben-David and Waring (Science and Technology for the Built Environment, 2018) modeled four office cases and found that spaces served by a common mechanical system were reasonably homogeneous (given similar supply flows per area and some air recirculation), with the standard deviation among locations almost always under 20% of the mean. For building-grade sensors, sensor error generally outweighed that variation, and the authors conclude that improving sensor accuracy likely matters more than capturing spatial distribution.
The two studies differ in method (measured meeting rooms, modeled offices), and neither counts how often a problem room goes unnoticed. A practical reading of both is to put room-level sensors where occupancy or air supply differs most from the neighbors, such as meeting rooms, and to check the sensors before trusting the map.
Answering complaints with a record
No study cited here measured whether monitoring changes the number of complaints. A log turns "the room is stuffy" into a question about what that room did between two times, which can be answered. Complaints and measurements can also disagree. In a one-year Montreal field test summarized by NIST (Emmerich and Persily, NISTIR 6729, 2001), one office floor had CO2-based demand-controlled ventilation and another floor served as a control. The floor with CO2-based ventilation control saved 12% of annual energy, and its occupants complained significantly more about the indoor environment, although measurements showed no significant contaminant concentration differences between the floors.
Two workplace rules touch on ventilation. Germany's ASR A3.6 (January 2012, last amended 2018) treats CO2 as a recognized measure of air quality where people are the main source of pollutants. It says measurements are normally not required and are to be made only where there is a justified suspicion of excessive CO2, and that measures taken for readings between 1,000 and 2,000 ppm are to be documented in the risk assessment. HSE's guidance says employers must make sure there is adequate ventilation in enclosed areas of their workplace. A continuous record is one way to support that documentation (reasoning, not a requirement of either text).
Cutting ventilation in rooms that are empty
A CO2 record that stays near outdoor level while fans run points to air delivered to empty rooms (reasoning from how CO2 behaves). NIST's 2001 review of CO2-based demand-controlled ventilation lists measured savings of 12% for the Montreal office floor and about 20% for a Minnesota high school, and calculated heating and cooling savings of 7.8% for a bank in Pasco, Washington, across six climates. Simulations in the review gave savings between 4% and over 50%. For open-plan offices, estimated energy-cost savings cited in the review (Meier, 1998; Mansson, 1994) are 20% to 30% at 40% average occupancy and 3% to 5% at 90%. A 2019 summary of ASHRAE research project RP-1747 reports simulated HVAC energy savings of 10% to 30% across climates for an office with realistic occupancy schedules, and says the approach was tested in simulation and lab-scale tests only.
The 40% and 90% occupancy estimates point the same way: the saving depends on how empty the rooms are. Air quality monitoring in offices shows that for a given building before any control is changed. Demand-controlled ventilation for commercial buildings covers the controls themselves.
Control and reporting both need a sensor that reads true. LBNL-3279E evaluated 208 single-location CO2 sensors in 34 commercial buildings and checked 90 of them at several concentrations. At 1,010 ppm, 40% of the checked sensors had errors greater than 75 ppm, and the average absolute error was 138 ppm (14%). When asked, no facility manager said the sensors had been calibrated since installation. The study dates from 2010, so it describes the sensors of that period, and it is a reason to ask any supplier how a sensor is checked over its life.
Checking that a change worked
A new schedule, a repaired damper or a changed setpoint can be judged against a record taken before it. HSE advises repeating CO2 monitoring as the weather changes and recording occupant numbers and the ventilation in use, and the same applies to a before-and-after comparison: compare days with similar occupancy and weather (a practical suggestion). How to read ventilation data in five minutes shows the daily curve to compare.
On the EU side, Article 13(10)(d) of Directive (EU) 2024/1275 says the building automation and control systems required under Article 13(9) (non-residential buildings above 290 kW or 70 kW, where feasible) must be capable, by 29 May 2026, of monitoring indoor environmental quality. Point (d) names no parameters. National law decides which buildings that reaches, as set out in EPBD indoor environmental quality monitoring: what the May 2026 date means. Air quality monitoring in offices can help with compliance where the rule applies, and it does not decide whether a building is covered.
Nomestic's ClimateIQ platform measures indoor climate room by room (CO2, temperature, humidity and more), and the devices are wireless and battery-powered, so a room takes minutes to equip. It works with or without a building management system, and nothing in the existing HVAC gets replaced. Savings are verified by comparing measured data before and after a change.