How to read ventilation data in five minutes
A routine for one day of CO2 data: overnight baseline, morning rise, peak, plateau and recovery, with temperature and humidity beside it. What each pattern can mean.
Ventilation data from a room is easiest to read as one occupied day of CO2 in five looks: the overnight baseline, the morning rise, the peak, whether the curve flattens, and how fast it falls once people leave. Temperature and humidity go beside it for context. The meanings below are interpretations: the same CO2 curve can have more than one cause, and the data alone cannot always separate them.
Check the sensor before reading the ventilation data
ASHRAE's issue brief on indoor carbon dioxide says sensor accuracy, location and calibration are all critical for meaningful inferences. In the Lawrence Berkeley National Laboratory (LBNL) field study of 208 installed sensors, 40% were off by more than 75 ppm at 1,010 ppm. If a curve looks odd, first ask whether the sensor sits near a door, a supply diffuser or the people in the room (see where to place CO2 sensors for ventilation control) and whether anyone has checked its calibration.
A five-minute routine for one day of CO2
- Read the overnight baseline. Pick the hours before the first person arrives. In an empty room with air exchange, CO2 falls toward the outdoor level. Outdoor air is not a fixed 400 ppm: NOAA's Mauna Loa monthly mean for September 2026 was 426.07 ppm (preliminary), and LBNL found one building whose outdoor CO2 reading averaged approximately 510 ppm. A baseline that stays high can mean the room kept air from the previous day, someone was in the room, or the sensor reads high. A baseline at about 400 ppm every night can mean an empty, well-ventilated room, or a self-calibrating sensor that treats its lowest readings as 400 ppm (Sensirion's data sheet and LBNL both describe that assumption). The data alone cannot say which.
- Follow the morning rise. CO2 starts to climb when people arrive. NIST Technical Note 2213 models an office at 0.5 air changes per hour and 5 people per 100 m², with everyone entering at once: 239 ppm above outdoors after one hour, 383 ppm after two hours, and almost 6 hours to reach steady state. A real room will differ, so the shape of the curve is more useful than the numbers. A steep first hour that bends over fits that model. A rise that stays steep for hours suggests many people for the air supplied, and a room that hardly moves on a full day of use suggests a large air supply or fewer people than assumed.
- Mark the peak and the headcount. Note the highest value during occupied hours, when it happened and how many people were there. ASHRAE's issue brief on indoor carbon dioxide says interpretation needs the number and activity of occupants relative to design capacity and the time since occupancy began, and the UK Health and Safety Executive (HSE) advises recording occupant numbers and the ventilation in use with each reading. Compare the peak with the guide values in what is a good CO2 level in an office. A narrow spike of a few minutes can come from a person breathing near the sensor or a crowd arriving, and says little about the ventilation. LBNL reported that concentrations at wall points in meeting rooms sometimes fluctuated rapidly, potentially in part because of exhaled breath from people near the sample points. For spaces up to 50 m², the HSE says monitors are unlikely to give reliable measurements where the number of people changes over short amounts of time.
- See whether the curve flattens. NIST Technical Note 2213 says concentration reaches steady state only if airflow and CO2 generation stay constant, and that a room is essentially at steady state after three time constants, where the time constant is the inverse of the air change rate. At 1.0 air change per hour that takes 3 hours, and at 0.5 it takes 6. A flat top can then mean people and airflow were roughly constant, and its height above outdoors reflects the outdoor air per person: ASHRAE's technical FAQ ties about 700 ppm above outdoors to about 7.5 L/s per person at typical office activity. A curve that keeps climbing all day has not reached steady state. A sudden step down with the same people in the room can point to an airflow change, such as a damper moving or a window opening.
- Watch the fall after people leave. With the room empty, CO2 generation stops and the level falls toward the outdoor level. ASTM D6245-25, as described on the ASTM store page, says the decay of indoor CO2 concentrations can be monitored in a building after the occupants have left. In the NIST mass balance the same time constant would govern the fall. That last point is reasoning from the equation, which the note does not present as a measurement method, so the speed of the fall is a cue to check further. A quick fall suggests air is being exchanged. A slow fall, or a level that stays high into the evening, suggests little air is moving, for example because ventilation stopped at the end of the workday. If CO2 is already at the outdoor level overnight while the fans run, three signs your ventilation runs when nobody is there covers the energy side.
Temperature and humidity beside the CO2 curve
Temperature and humidity answer different questions from CO2, so read them as separate curves on the same day. ISO 17772-1, as presented in Bjarne Olesen's 2023 slides (DTU), recommends category II design temperatures for sedentary work of 20.0 to 24.0 °C in the heating season and 23.0 to 26.0 °C in the cooling season. The slides assume relative humidity of 40% in the heating season and 60% in the cooling season for those calculations. These are calculation assumptions, and the slides give no humidity range to check a day of data against.
The rest is interpretation. If the CO2 curve looks healthy and the temperature leaves the range, the cause is more likely in heating or cooling than in the fresh air supply. If CO2 and temperature both climb through the afternoon in a full room, the room may be short of both air and cooling.
What a single day of ventilation data cannot tell you
One room on one day is a small sample of ventilation data. The HSE advises repeating monitoring as the weather changes because natural ventilation differs. ASHRAE's issue brief on indoor carbon dioxide says indoor CO2 does not indicate the air quality of a building as a whole. Comparing the same room across several days, and a weekday with a weekend, shows whether a pattern repeats. This is a practical suggestion, not a published finding. A pattern that repeats is worth a check at the equipment.