Technology
Why most buildings ventilate on a schedule instead of on need
Ventilation is sized for the fullest room and switched by a clock. Why schedules are the default, and what changes when airflow follows a measured signal.
Ventilation control in many buildings is a schedule: a fixed airflow sized for the fullest the room will ever be, started and stopped by a clock. A US Department of Energy (DOE) federal technology alert on CO2 sensors (DOE/EE-0293, listed in a library catalog as March 2004) says many HVAC systems ventilate at a constant fixed level, usually the level prescribed for full occupancy. Demand controlled ventilation (DCV), where airflow follows a measured signal, asks for more: equipment that can change its airflow and sensors that stay accurate.
Standards size ventilation for the fullest room
ASHRAE Standard 62.1 calculates outdoor air for a zone from a rate per person and a rate per unit of floor area. A March 2012 review by Pacific Northwest National Laboratory (PNNL) says the 2004, 2007 and 2010 editions use that combination, and describes the zone population as the largest number of persons expected to occupy the zone during typical use. The calculation starts from the peak.
Take the Table 6-1 values as printed in addendum w to Standard 62.1-2022 (approved 30 September 2025). Office space and meeting rooms both carry 5 cfm per person and 0.06 cfm per ft². The default density is 5 people per 1,000 ft² in an office and 50 in a conference or meeting room.
Worked out from those values, the breathing-zone outdoor airflow per 1,000 ft² is 85 cfm for office space and 310 cfm for a meeting room. The full procedure adds corrections, so these are starting values. A meeting room is sized for its fullest meeting.
The same logic reaches the air terminals. PNNL's March 2012 literature review says the minimum airflow of a variable air volume (VAV) terminal box is commonly set to a fixed value tied to the zone's design occupancy. It adds that integrators and installers often set that minimum at 30% to 50% of maximum airflow, and that conference rooms often receive the airflow designed for full occupancy even when they are empty.
Energy codes already ask for time controls
One US example is the commercial provisions of the Washington State Energy Code (WAC 51-11C-40342, section C403.4.2.2, automatic setback and shutdown, as archived in 2024). It calls for automatic time clock or programmable controls that can start and stop the system on seven different daily schedules per week, and for a manual override that allows temporary operation for up to 2 hours, a manually operated timer for up to 2 hours, or an occupancy sensor. The rule that applies depends on where the building is.
A schedule is itself an accepted way to estimate occupancy. PNNL's review lists timers, occupancy schedules, occupancy sensors, population counting and CO2 sensors as acceptable ways to define occupancy in the 2010 edition of Standard 62.1. A measured signal needs sensors. According to the same review, the 2010 edition of ASHRAE Standard 90.1 requires demand controlled ventilation in dense spaces (over 500 ft² with a design occupancy above 40 people per 1,000 ft², on certain system types) and exempts multiple-zone systems without direct digital control of individual zones that communicate with a central control panel.
Where the schedule and the room part ways
The DOE alert gives two case studies. In a 30-story office building in Birmingham, trend logging over 7 days at one location, before a CO2-based retrofit in 2001, found peak levels averaging 674 ppm. The report equates that to more than 34 cfm per person against a design need of 20, or 170% of design. At an office building on Beaufort Marine Corps Air Station in South Carolina, the base utilities director said the building was designed for 500 people and that occupancy is rarely over 100. Two buildings in one report cannot say how common this is.
A wider figure comes from Lawrence Berkeley National Laboratory (LBNL). Its April 2010 report on California's Title 24 says national level data indicate average minimum ventilation rates in offices of either 28 or 80 cfm per person, the difference coming from different measurement protocols, against a California minimum of approximately 15 cfm per person.
Assumed occupancy can be off as well. Duarte, Van Den Wymelenberg and Rieger (Energy and Buildings, 2013) analyzed occupancy sensor data from one large multi-tenant office building. Their occupancy diversity factors differed by as much as 46% from the ASHRAE 90.1-2004 energy cost method values.
What changes when ventilation control follows a measured signal
Airflow stops being one number. Mysen and colleagues (REHVA Journal, 2015) write that a DCV system will typically have airflow rates between 30% and 80% of the maximum. The area part of the requirement stays, so (as general reasoning) the floor sits above zero unless an empty-zone mode applies. ASHRAE's 2019 report on research project RP-1747 names one, the occupied-standby mode in Standard 62.1, which allows zone ventilation to be reduced to zero when a zone is detected to be empty. The report does not name the edition. The project's control sequence accounts for that mode and was tested in simulations and lab-scale tests.
Ventilation control on a measured signal makes the sensor something to maintain. LBNL checked 208 CO2 sensors in 34 commercial buildings. At about 1,010 ppm, 40% had errors above 75 ppm and 13% above 300 ppm, and sensor age did not reliably predict error. In the field studies behind its Title 24 report, no facility manager reported calibrating CO2 sensors after the initial installation. As general reasoning, a schedule has no sensor to calibrate.
The payoff is uneven. The DOE alert finds the most energy-saving potential where occupancy fluctuates during a 24-hour period, is somewhat unpredictable and peaks at a high level. Its case studies generally show greater savings for heating than for cooling, and it says applications in moderate climates may show little energy or cost saving, especially where economizer operation contributes substantially to cooling. The REHVA paper, citing Mysen and colleagues (2010), says the energy saving potential of demand controlled ventilation is seldom met in evaluations of real energy use. A room with a steady pattern of use may be well served by a schedule. The article on ventilation control compares schedule, CO2 and occupancy signals, and demand-controlled ventilation covers the standards and the savings studies.
The practical question for an owner is which rooms differ most from their schedule. As general reasoning, a room's CO2 overnight shows when it is empty and its daily peak shows how full it gets, and both can be set against the hours the system runs. How to read ventilation data in five minutes walks through a day of CO2 data.
Nomestic measures indoor climate room by room, including CO2, temperature and humidity, and works with or without a building management system (BMS). Nothing in the existing HVAC gets replaced.