← All articles

Health

Building complaints are a data problem, not a people problem

Ventilation and temperature readings explain some indoor climate complaints. Other symptom reports track work stress and control over the room. What the research found, and how to triage.

A speech bubble reading 'too warm' connected by a line to a small chart of room temperature over a day

Indoor climate complaints such as "it is too warm" or "the air is stale" come without a reading unless someone records one, and often without an exact room or time. The title's claim holds in part. Data can sort complaints into those with a measurable cause and those without. The research also finds symptom reports that measurements do not explain, and the strongest evidence for that, the Whitehall II study below, points to work stress and control over the environment. The people side stays in the picture.

What investigations of problem buildings found

By December 1987, NIOSH had conducted 484 indoor air quality investigations. A 1989 paper by Bierbaum, Gorman and Wallingford reports that the symptoms were too diverse and nonspecific to identify a causative agent, and that the problems found included contamination from building materials, microbiological contamination, contamination from outside and inside the building, and inadequate ventilation. The OSHA Technical Manual, citing NIOSH data from 1989 on approximately 500 investigations, puts inadequate ventilation at 52% of primary sources, contamination from inside the building at 16%, from outside at 10%, microbial contamination at 5%, building fabric at 4% and unknown sources at 13%. These are investigated problem buildings, not a sample of all buildings (reasoning), and the data are from the 1980s.

A 1993 study of 12 public office buildings near San Francisco (Fisk et al., Indoor Air) surveyed 880 occupants. Symptom prevalence varied widely between buildings, and the ratio of the highest to the lowest was always above three. Occupants of mechanically ventilated and air-conditioned buildings reported significantly more symptoms than occupants of naturally ventilated ones. Measures of thermal discomfort did not significantly improve the statistical models, which conflicts with earlier studies, and the authors could not explain why.

A 2004 article by P. S. Burge in Occupational and Environmental Medicine defines sick building syndrome as a group of mucosal, skin and general symptoms that are temporally related to working in particular buildings. The average number of work-related symptoms per occupant is known as the building symptom index. Burge notes that "sicker" buildings often have air temperature, humidity and lighting that fully comply with current standards, and that air-conditioned buildings generally have a higher prevalence of symptomatic workers than naturally ventilated ones.

Where measurements explain indoor climate complaints

A 1999 review in Indoor Air (Seppänen, Fisk and Mendell) covered 20 ventilation studies with close to 30,000 subjects. Almost all found that ventilation rates below 10 L/s per person were associated with significant worsening in one or more health or perceived air quality outcomes. For CO2, 21 studies with over 30,000 subjects were reviewed, and about half suggested the risk of sick building syndrome symptoms kept falling significantly as CO2 dropped below 800 ppm.

A 2000 analysis of 41 office buildings from the EPA BASE study (Apte, Fisk and Daisey, Healthy Buildings 2000) found odds ratios of 1.2 to 1.5 per 100 ppm of CO2 above the outdoor level (workday average) for sore throat, nose and sinus symptoms, tight chest and wheezing. The paper's conclusions give the range as 1.1 to 1.5. The authors state that there is no direct causal link between CO2 and the symptoms, that CO2 is approximately correlated with other indoor pollutants, and that the conclusions hold for buildings where the workday average CO2 stayed below 800 ppm.

Studies of temperature complaints give mixed results. In six offices in Tehran (Nasrollahi, Knight and Jones, 2008), perceived thermal sensation agreed well with the calculated predicted mean vote in four of them, and more than half of the offices did not meet the comfort levels recommended in ASHRAE Standard 55 and ISO 7730. A 2020 field study of air-conditioned offices in Singapore and Thailand (Frontiers in Built Environment; data loggers and a questionnaire, 2017 to 2019) found that most measured conditions fell within the ASHRAE 55 comfort zone for 1.0 clo, yet occupants were often dissatisfied because the offices were overcooled. Symptoms were most likely in the coldest group, at 21 to 22°C. The comfort temperatures the authors derived sat above the measured indoor values, and they attribute the gap to clothing adaptation and individual complaints.

In the Center for the Built Environment occupant survey, with more than 90,000 respondents in about 900 buildings (Graham, Parkinson and Schiavon, Buildings and Cities, 2021), 39% were dissatisfied with temperature. Only sound privacy, at 54%, scored worse, and noise level followed at 34%.

Where people factors still matter

In the Whitehall II study (Marmot et al., Occupational and Environmental Medicine, 2006), 4,052 civil servants aged 42 to 62 in 44 office buildings answered a self-report questionnaire on 10 symptoms and on psychosocial work stress, and the answers were linked to cross-sectional data on the buildings' physical environment. After adjusting for age, sex and employment grade, most physical measures showed no significant relation to symptom prevalence. Stronger effects appeared for high job demands and low social support. In the multivariate analysis only psychosocial work characteristics and control over the physical environment were independently associated with symptoms. The authors conclude that the physical environment appears less important than features of the psychosocial work environment in explaining differences in symptom prevalence.

The studies support a split, though none of them states it. Where a reading is out of range, as in the Tehran offices and the ventilation studies, a complaint points to something measurable. Where readings sit inside the range and people are still unhappy, the cause may lie elsewhere. In the Singapore and Thailand offices the reference comfort zone did not match what occupants preferred, and in the Whitehall II buildings the stronger associations were with job demands, low support and control, so a better reading would not settle those cases. This is reasoning from the studies.

Treating each complaint as a data point

The EPA and NIOSH guide Building Air Quality (1991) advises logging IAQ-related complaints. Its incident log records a file number, the date, the problem location, the outcome or comments, and the initials of the person making the entry. The guide uses the spatial pattern of complaints to define the complaint area, looks for daily, weekly or seasonal cycles, and treats a change that reduces complaints as support for a hypothesis about the cause.

A suggested triage for indoor climate complaints (practice, not a published method) adds the room's CO2, temperature and humidity at the time of each complaint. A reading outside its range points to something measurable, for example the equipment or its controls, and how to find the cause room by room covers that branch. A reading inside the range sends the follow-up to the room itself: drafts, clothing, local control, how many people use it. Several complaints from one room or one time of day point to a pattern worth a look before the next call, which how to spot ventilation problems before tenants complain takes further.

The data used to triage indoor climate complaints has limits. In the LBNL study of 208 CO2 sensors, 40% were off by more than 75 ppm at 1,010 ppm (Fisk et al., 2010). An ASHRAE Technical Committee 4.3 FAQ states that CO2 is not a good indicator of the concentration and occupant acceptance of other indoor contaminants. A normal reading can therefore sit next to a real complaint, and that is a reason to ask the occupant. Indoor air quality and tenant satisfaction looks at what developers can measure.

Get ready for the BACS regulation without changing your existing HVAC infrastructureOptimize indoor climate and energy efficiency without changing your existing infrastructure