How to spot ventilation problems before tenants complain
Logged readings and a walk-round can show ventilation faults before a complaint arrives. Published fault studies report how common faults are in monitored buildings.
Spotting ventilation faults early through monitoring means looking at how rooms behave when nobody has reported anything, and keeping a record that ties every complaint to a room and a time. Ventilation faults here means equipment or control problems that leave a room with the wrong amount of outdoor air or the wrong temperature. That is practical advice. The published fault data below shows how common reported faults are in monitored buildings.
What the data says about ventilation faults
A 2023 study by researchers at LBNL and partner institutions (Crowe et al., Science and Technology for the Built Environment) analyzed fault reports from monitoring software on over 60,000 pieces of HVAC equipment. On any given day, 40% of air handling units and 30% of air terminal units had at least one reported fault. The most common air handling unit fault was the supply air temperature setpoint, found on 55% of units at some point in the monitored period. For air terminal units, faulty zone temperature sensors and abnormal zone temperature were each found on 46% at some point. Eighteen air handling unit faults persisted for more than 20% of the time period covered by the data.
These counts have limits that the authors name. The software can produce false positives and false negatives, fault thresholds likely differ between tools, the sample is not demonstrated to be representative of US commercial buildings, and owners who invest in fault detection may have above-average buildings. The data do not explain why faults persist. The counts are of reported faults, so they cannot show how many of them a tenant noticed (reasoning), and no source cited here reports how long faults run before a complaint arrives.
Early signs of ventilation faults in the data
Equipment running outside occupied hours. DOE's 2013 retrocommissioning guidance lists problems to look for in building automation trend data in large commercial buildings, including occupied schedules that are longer than needed, equipment running during unoccupied periods (exhaust fans, lights, circulation pumps), air handlers heating and cooling at the same time, and economizers that bring in too much outside air. A diagnostic tool sheet from Seattle's Tune-Up Accelerator lists loggers that record the start and stop operation of fans, pumps, chillers and boilers so it can be checked against the occupancy schedule. Standalone loggers do not need a BMS, and waste of this kind may never prompt a complaint, so the review has to go looking for it (reasoning). Where ventilation wastes energy covers what to check first.
CO2 that stays high while a room is occupied. The EPA and NIOSH guide Building Air Quality (1991) calls peak CO2 over 1,000 ppm an indicator of underventilation. The UK Health and Safety Executive says CO2 consistently above 1,500 ppm in an occupied room indicates poor ventilation, that single readings can mislead, and that several measurements through the day should be taken with occupant numbers and the type of ventilation recorded. The Seattle sheet also lists a CO2 meter and logger among the tools for spotting ventilation rates that may differ from ASHRAE 62.1, with outside air measured at the minimum damper position. What is a good CO2 level in an office gives the standards' numbers.
Readings that look wrong. An NREL analysis of fault data from rooftop units in small-box retail stores (Shoukas, Bianchi and Deru, 2020) found that most of the "sensor failure" faults in the data from two fault detection products were not sensor failures: they were space temperature or humidity readings outside setpoint, which could indicate a performance issue such as inadequate space conditioning, while extreme or negative values may indicate a broken sensor or bad wiring. A DOE field check of rooftop units, reported on a 2021 peer review slide, compared the building automation reading with a separate logger at a 2°F (about 1 K) threshold and flagged 3 of 11 units (27%) for zone temperature sensor drift. The slide says the analysis was in progress and not yet cross-checked. In the LBNL study of 208 CO2 sensors, 40% were off by more than 75 ppm at 1,010 ppm (Fisk et al., 2010). An odd reading is either the room or the sensor, and both need checking.
A room that differs from its neighbors. Rooms of the same type and use should follow similar daily curves. A room that drifts away from them is a candidate for a look before anyone calls. This is a practical suggestion and no source cited here tests it.
Early signs on a walk-round
Two walk-round items come from the sources: the EPA and NIOSH guide notes that furniture, papers or other materials can interfere with air movement around thermostats, and a DOE case study lists relocating thermostats to improve comfort and avoid simultaneous heating and cooling. Other items are practice, not published findings: blocked supply or return openings, and doors or windows propped open against the HVAC. Walk the rooms that have the readings described above first.
What to log, and how often
The EPA and NIOSH guide recommends a system for logging IAQ-related complaints. Its incident log records a file number, the date, the problem location, the forms used, the outcome or comments, and the initials of the person making the entry. Its occupant diary asks for the time and date, the location, the symptom, its severity and duration, and comments. It also tells investigators to use the spatial pattern of complaints to define the complaint area and to look for daily, weekly or seasonal cycles and weather-related patterns. Adding the room's logged CO2, temperature and humidity at the time of the complaint turns each complaint into a data point (practical suggestion). Building complaints are a data problem takes that argument further.
For ongoing monitoring, a 2025 model regulation text by the Nordic Ventilation Group, REHVA and Eurovent, which is an example and not binding law, says monitored IAQ data should be available at hourly resolution for the last 12 months in building automation and control systems. No source cited here sets a review interval. A weekly look at trends and a monthly look at room-to-room differences is a practical starting point (practice, not a published interval), and a simple weekly routine for reviewing building data sets one out.
Nomestic measures indoor climate room by room (CO2, temperature, humidity and more) and works with or without a BMS. The devices are wireless and battery-powered, so a room takes minutes to equip.