Where ventilation wastes energy: what to check first
Seven places where ventilation wastes energy, in the order that is cheapest to check: operating hours, airflow settings, simultaneous heating and cooling, economizers, filters, ducts and heat recovery.
Energy waste in ventilation comes from a short list of repeatable causes. The Pacific Northwest National Laboratory (PNNL) says between 10 and 30% of the energy used in commercial buildings is wasted because of improper and inefficient operation, and the page cites no source for the figure. The US Department of Energy's O&M Best Practices Guide (Release 3.0, August 2010) cites an estimate from 1999 that operations and maintenance programs aimed at energy can save 5 to 20% on energy bills without significant capital investment. Both figures cover the whole building, not ventilation alone.
The order below is a practical suggestion for HVAC optimization: control settings first, because they cost the least to check and change, then problems that need measurement or equipment work. Each item names the source behind it.
Check hours of operation first
PNNL's Re-tuning Measure Guide (PNNL-SA-183964, April 2023) states that dedicated outdoor air systems and exhaust systems should not be enabled after hours or during start-up before occupancy. It lists a separate measure for closing minimum outdoor air dampers at night, on weekends and during start-up, and it says to make sure bathroom exhaust fans are not interlocked with supply fans. A PNNL re-tuning training chapter for small and medium-sized commercial buildings (PNNL-SA-92685, 2013) says exhaust fans with time clocks should be programmed to run only when needed, that fans without them can be given time clocks, and that the payback of such measures is in most cases less than 1 to 2 years.
The evidence of this energy waste is in the trend data. The same chapter says meter profiles reveal inconsistent usage but need hourly or 15-minute data. It also says an 'Auto' fan setting may not meet ventilation code requirements and suggests a 'Fan-On' setting while the space is occupied, which raises electricity use, so cutting hours has a lower limit. Three signs your ventilation runs when nobody is there covers simple ways to see it.
Energy waste from airflow above need
A 2012 PNNL literature review (PNNL-21281) says constant minimum airflow set points based on rules of thumb are still common in the field, and that a minimum set higher than the zone requires means more fan power and more reheat than necessary. It reports that integrators and installers often set the minimum to between 30 and 50% of a terminal box's maximum airflow. The PNNL guide advises limiting minimum airflow to 10 to 15% of each VAV box's maximum.
Outdoor air follows the same pattern. The guide notes that many operational sequences are based on unrealistic design occupancy, and a PNNL economizer chapter asks whether the minimum outdoor air position is 20% or less, saying a higher value could be part of the problem with excess outdoor air and the energy needed to temper it. Excess is only waste where the air is not needed. The US Department of Energy's federal technology alert on CO2-based demand-controlled ventilation (DOE/EE-0293, early-2000s field data) quotes a controls company owner who warned that a chronically under-ventilated building might use more energy after demand control. Check CO2 before cutting airflow, and see demand-controlled ventilation for commercial buildings for the control side.
Simultaneous heating and cooling
Heating and cooling at the same time shows up in several places. The PNNL guide says thermostat dead bands should be at least 3 °F (preferably 4 °F). It says wildly different setpoints in adjacent zones can cause simultaneous heating and cooling within the floor. Minimum airflow set too high forces reheat, according to the 2012 review above. In PNNL's re-evaluation of eight dedicated outdoor air system sites (PNNL-34419, December 2023), the report attributes the poor efficiency of the original system at one site to a substantial amount of simultaneous heating and cooling.
A practical check, not a published procedure: plot heating and cooling valve positions for an air handler over a day. Both above zero at the same time is the symptom.
Economizers that do not economize
The guide says economizers are often found not working properly. The PNNL economizer chapter (PNNL-SA-85063, 2012) lists possible causes: an incorrect control strategy, stuck dampers, disconnected or damaged linkages, a failed actuator, disconnected wires and failed or miscalibrated sensors. Its trend checks are specific. With the outdoor-air damper command wide open, mixed-air temperature should be within 4 to 5 °F of outdoor-air temperature, allowing for supply fan heat. Dampers that are not open to economize under favorable conditions when outdoor temperature is between 40 and 60 °F are a flag. The chapter's example plots, both labeled bad operation, show a damper stuck closed that left good outdoor air unused and one stuck open that wasted heating energy.
Filter pressure drop
Eurovent Recommendation 4/24 (2023, update 1 published May 2024) says pressure drop rises as a filter loads with dust and bases filter energy on the average pressure drop over the filter's life, the operating hours and the fan efficiency. It states that a lower pressure drop saves energy only with a speed-adjustable fan holding airflow constant, and that on a fixed-speed fan a lower pressure drop gives a higher airflow. By the same logic a loaded filter on a fixed-speed fan mainly cuts the air delivered (general reasoning from that statement). The recommendation is a rough estimation method based on laboratory test data, whose conditions may differ significantly from the individual application, and this article cites no measured energy waste figure for a dirty filter in an occupied building. What to check is the pressure drop at which filters are changed and whether anyone logs it.
Duct leakage
Two LBNL field studies of light commercial rooftop systems in California found different leakage. Delp and colleagues (an ACEEE proceedings paper, year not printed on the copy read) tested 25 packaged rooftop systems in 16 buildings in northern California in the 1996 and 1997 cooling seasons. Average supply-side leakage was 26% of system flow, and only 61% of fan flow went through the registers. Xu, Modera and Carrie (also an ACEEE paper) tested five rooftop packaged systems in four buildings and found leakage averaging about 10% of supply fan flow, with a standard deviation of 6%. They attribute the difference from the earlier study to a combination of lower leakage levels and lower operating pressures.
Neither paper reports the resulting energy waste in kWh. Delp and colleagues give an average delivery efficiency of 65% for ten systems, which combines leakage and conduction losses. Both samples are small and cover light commercial systems, so they do not speak to large central plants. A practical suggestion, not from these papers: test duct leakage on the systems where ducts run through unconditioned ceiling cavities.
Heat recovery
Commission Regulation (EU) No 1253/2014, Annex III, sets a minimum heat recovery thermal efficiency for bidirectional non-residential ventilation units of 67% from 1 January 2016 and 73% from 1 January 2018 for systems other than run-around systems, and 63% and 68% for run-around systems. The regulation covers the placing on the market or putting into service of units, so an older air handler needs its own check: does it recover heat at all, and does the recovery stay on when outdoor air could do the cooling? A revision of the regulation was in draft in 2025 (Eurovent comments dated 20 May 2025), so the current figures should be checked. The PNNL guide says to aim to lock out heat recovery when it is appropriate to economize. The same heat exchanger limits demand-control savings, since the Department of Energy alert says demand-controlled ventilation may not reduce energy use in buildings with heat exchangers. This article cites no source for the retrofit cost or savings of adding heat recovery to an existing unit, so that needs a calculation for the unit in question.
The PNNL re-tuning training chapter recommends repeating re-tuning quarterly or at least every six months, or sooner when energy consumption rises or occupant complaints increase. The first pass can run on trend data the building already holds, such as fan status, damper and valve positions and room CO2. For measures that fit an existing plant, see improving ventilation without replacing your HVAC. Nomestic works as an energy management system for ventilation and HVAC and flags runtime and airflow that do not match how rooms are used.