← All articles

Technology

Improving ventilation without replacing your HVAC: what is possible

An HVAC retrofit that keeps the plant can fix schedules, airflow settings and controls. Filters and heat recovery are limited by the fans and ducts already installed. What the sources say.

An existing air handler outline with small control and sensor symbols added along its airflow path

A lot can change in an HVAC retrofit that leaves the plant in place. Schedules, setpoints, minimum airflow, outdoor air settings and controls can all be changed on existing equipment, and the savings from that kind of work are documented. What a retrofit cannot change is capacity: the fans, coils, ducts and dampers that are installed set the limits on filters, airflow and demand control.

Start with re-commissioning and re-tuning

A practical starting point in an HVAC retrofit is to fix what already exists before adding anything. LBNL's 2009 assessment of commissioning projects covers 643 buildings, about 99 million square feet across 26 states, drawn from 37 commissioning providers. For existing buildings it reports median whole-building energy savings of 16%, a median payback of 1.1 years and a median cost of $0.30 per square foot. PNNL's re-tuning approach is narrower: low-cost and no-cost control changes to building automation systems. In a paper by Fernandez, Taasevigen and Underhill in the ASCE Journal of Architectural Engineering, a set of 26 federal office buildings and courthouses achieved average annual energy savings of 12.1%, from baselines benchmarked as very efficient on average. The US Department of Energy's O&M Best Practices Guide (Release 3.0, August 2010) cites a 1999 estimate that operations and maintenance programs targeting energy efficiency can save 5 to 20% on energy bills without a significant capital investment.

The LBNL figures come from projects of 37 commissioning providers and the PNNL figures from federal buildings in the United States, so they show what has been achieved, and a given building may get less or more. A PNNL re-tuning training chapter (PNNL-SA-92685, 2013) suggests repeating re-tuning quarterly or at least every six months.

Schedules, setpoints and airflow limits

The PNNL Re-tuning Measure Guide (PNNL-SA-183964, April 2023) lists the changes that need no new equipment. Dedicated outdoor air and exhaust systems should not be enabled after hours or during start-up before occupancy. Where optimal start is in place, schedules can start 30 minutes before occupancy. The guide notes that many operational sequences are based on unrealistic design occupancy and says to determine rough compliance with ASHRAE 62.1 and reduce any excess default ventilation rates. VAV box minimum airflow can be limited to 10 to 15% of each box's maximum. The cost-saving side is covered in where ventilation wastes energy.

The same measures can raise ventilation where it is too low. A 2012 PNNL literature review (PNNL-21281) notes that a minimum airflow for ventilation that is too low may cause indoor air quality issues, and a PNNL re-tuning training chapter says an 'Auto' fan setting may not meet ventilation code requirements. The US Department of Energy's federal technology alert on CO2-based demand-controlled ventilation (DOE/EE-0293, early-2000s field data) quotes a controls company owner who warned that in a chronically under-ventilated building demand control might increase energy use, and who added that it can still correct indoor air quality problems. General reasoning: a retrofit that raises airflow where a room needs it counts as an improvement even when the energy bill goes up.

Measure airflow instead of reading it from a damper. The 2012 review states that on pressure-dependent boxes the damper position cannot be relied on to deliver the required airflow, and that pressure-independent boxes need an accurate flow measurement station to control at low minimum flows.

Controls upgrades and demand control in an HVAC retrofit

Demand-controlled ventilation depends on what the unit can already do. The federal technology alert says the technique is suitable only when there is a means of automatically adjusting the ventilation air supply, says properly functioning modulating dampers are necessary and says pneumatic controls will need to be replaced with electronic or direct digital controls. Sensors can be added to an existing system. The Government of Alberta's Design and Technology Series 20 (August 2025) adds that in systems running on 100% outdoor air the fans and VAV boxes have a limited turn-down ratio, and that the minimum fan speed is often the limiting factor in the minimum outdoor air rate. Adding demand-controlled ventilation to a building without a BMS walks through the work step by step.

Savings need realistic expectations. A REHVA Journal article on commissioning demand-controlled ventilation (Mysen and colleagues, 2015) says a working system typically runs at 30 to 80% of maximum airflow, and that evaluations of real energy use show the saving potential is seldom met. The PNNL 2012 review calls CO2-based control at each terminal box impractical because of the need for frequent recalibration (for example, annually) and the high cost of installing a sensor in each zone or room. That is a statement about control at every box. General reasoning, not from the review: measuring rooms first shows where control would pay off. Demand-controlled ventilation for commercial buildings covers the savings studies.

Filter upgrades

A higher-grade filter usually has a higher pressure drop, and the existing fan has to cope with it (general reasoning). Eurovent Recommendation 4/24 (2023, update 1 published May 2024) bases filter energy on the average pressure drop, the operating hours and the fan efficiency. It says that a lower pressure drop saves energy only with a speed-adjustable fan holding airflow constant, and that otherwise the volume flow rises. General reasoning from that relation: with a fixed-speed fan a filter with a higher pressure drop will reduce the airflow, so airflow should be measured before and after any filter change.

Heat recovery where feasible

Of the measures in an HVAC retrofit, heat recovery is the one most tied to the unit itself. Commission Regulation (EU) No 1253/2014 sets minimum heat recovery thermal efficiencies for bidirectional non-residential ventilation units: 67% from 1 January 2016 and 73% from 1 January 2018 for systems other than run-around systems, and 63% and 68% for run-around systems. The minimums apply to units placed on the market or put into service from those dates. A revision of the regulation was in draft in 2025 (Eurovent comments dated 20 May 2025), so the current figures should be checked. This article cites no source for the cost or savings of adding heat recovery to an existing unit, so any estimate needs a calculation for the unit and duct layout in question.

Nomestic measures indoor climate room by room, including CO2, temperature and humidity, and works with or without a building management system (BMS). Nothing in the existing HVAC gets replaced, and operators can override automatic adjustments at any time. The devices are wireless and battery-powered, so a room takes minutes to equip.