Gym ventilation: requirements, CO2 and what to monitor
ASHRAE 62.1-2022, English guidance and field data on gym ventilation: what the numbers say about CO2, heat and humidity, and what to monitor.
In ASHRAE Standard 62.1, gym ventilation is specified as outdoor air per person plus outdoor air per unit of floor area, and ASHRAE's issue brief on indoor carbon dioxide says the standard contains no CO2 limit based on human health and comfort. What sets a gym apart is the load. People who are exercising breathe out more CO2 than people at desks, Sport England's guidance for fitness spaces points to heat and humidity loads as well, and a class puts many of them in one room at once.
Why a gym differs from an office
CO2 output follows effort. In the method of Persily and de Jonge (AIVC conference paper, 2017), a person's CO2 generation is basal metabolic rate times activity level in met, so doubling the effort doubles the output. For men aged 21 to under 30 their table gives 0.0039 L/s at 1.0 met, 0.0120 L/s at 3.0 met and 0.0160 L/s at 4.0 met, and it stops at 4.0 met.
Breath changes too. In a PNAS study on a cycle ergometer (Mutsch et al., 2022; 16 healthy adults according to Physics World), aerosol emission rose only moderately up to about 2 W per kg of body weight and exponentially above it. TUM's press release on the study says the data give only indirect information on virus in exhaled air. Resistance exercise was not tested.
Heat and humidity are part of the load too. Sport England's design guidance for fitness spaces says the system serving a fitness gym must cope with heat loads, body odours and humidity. In a field study of eight Portuguese health clubs (Peixoto et al., 2023), relative humidity was higher in the group studios than in the cardio and bodybuilding areas in five of the eight clubs.
Gym ventilation requirements in ASHRAE Standard 62.1
Table 6-1 of ANSI/ASHRAE Standard 62.1-2022 sets outdoor air per person (Rp) and per floor area (Ra) by space type. The standard is paywalled. The rows below are as printed in addendum ab to the 2022 edition, which ASHRAE posts on its site.
- Health club/aerobics room: 20 cfm (10 L/s) per person plus 0.06 cfm/ft2 (0.3 L/s per m2), default density 40 people per 1,000 ft2, air class 2.
- Health club/weight rooms: the same rates, default density 10 people per 1,000 ft2, air class 2.
- Gym, sports arena (play area): 20 cfm (10 L/s) per person plus 0.18 cfm/ft2 (0.9 L/s per m2), default density 7 people per 1,000 ft2, air class 2.
The same table lists office space at 5 cfm (2.5 L/s) per person plus 0.06 cfm/ft2, at 5 people per 1,000 ft2. The per-person rate for a health club is four times the office rate.
Addendum w, approved on 30 September 2025, adjusts the default occupant densities in Table 6-1 to stay within the 2024 International Building Code allowances. The posted addendum text does not show which rows changed, and its aerobics row carries figures it does not explain. The aerobics density and CO2 values here are those of addendum ab, so check the current table before using any of them in a design.
What English guidance says
Approved Document F, volume 2 (2021 edition, in use from 15 June 2022) is for England only, and the points below are guidance. Paragraph 1.21 says that in new buildings, occupiable rooms where singing, loud speech or aerobic exercise or other aerosol generating activities are likely to take place should have a means of monitoring indoor air quality, which may be CO2 monitors or other means. Paragraph 1.22 excludes rooms up to 125 m3 or 50 m2 and rooms over 800 m3 or 320 m2. It gives no ventilation rate for gymnasiums and names Sport England's guidance instead.
Its Appendix C says a consistent indoor CO2 value below 800 ppm is likely to indicate a well ventilated space, and that an average of 1,500 ppm over the occupied period is an indicator of poor ventilation. Where there is dancing, playing sport or exercising, it recommends enough ventilation to keep CO2 below 800 ppm.
Sport England's design guidance note on fitness and exercise spaces (Issue 002, March 2008, as reproduced in a Woking planning document) lists a minimum of 20 L/s per person of fresh air at peak occupancy for a fitness gym and for studios. It gives 16 to 18 °C for the gym, 18 °C for studios and relative humidity preferably below 60%, and no air change rates. The 20 L/s is twice the 10 L/s per person in the ASHRAE health club rows, which also add an area-based rate.
What EN 16798-1 says about gyms
According to a REHVA Journal summary (Olesen, 06/2024), EN 16798-1:2019 sorts requirements into categories I to IV, with per-person rates of 10, 7, 4 and 2.5 L/s for non-adapted persons. The summary names no gym or sports space. The standard is paywalled, so no EN 16798-1 value for gyms is given here.
What CO2 readings mean in a gym
Addendum ab adds a column, maximum CO2 above ambient, to Table 6-1 for CO2-based demand-controlled ventilation. The values are 1,500 ppm for the aerobics room and the weight rooms, 900 ppm for the gym play area and 600 ppm for office space. Ambient may be assumed to be 400 ppm, so by Equation 6-12 the control ceiling for an aerobics room at default density is 1,900 ppm (addendum ab values; see the note on addendum w above). The addendum says these values are not intended to be used as indicators of indoor air quality. They come from steady-state equations at default occupant density.
One gym can therefore be read against 800 ppm (English guidance for high physical activity), 1,500 ppm as an average (English indicator of poor ventilation) and a 1,900 ppm control ceiling (ASHRAE). They answer different questions. ASHRAE's issue brief on indoor carbon dioxide says CO2 readings far above expected ranges may indicate a ventilation system that is not working properly, and lists occupant numbers and activity against design capacity among the factors to consider.
Field data are thin. Peixoto et al. (2023) measured eight health clubs of one low-cost chain around Porto for 12 days each, under COVID-19 occupancy and ventilation restrictions. They report CO2 in mg/m3, not ppm: an average of 1,489 and 1.1 to 1.4 times higher in group studios than in cardio and bodybuilding areas. The average was below the Portuguese protective value of 2,250 mg/m3 that the paper cites. The highest studio median, 2,538 mg/m3 in one club, was above it. One chain, one region and pandemic rules limit how far this carries.
What to monitor in a gym
The list below is a practical suggestion, not a published method.
- CO2 in each room that holds a class or a crowd: studios, weight areas, cardio floors, reception. ASHRAE addendum ab places sensors used for demand control 0.9 to 1.8 m above the floor.
- Temperature and relative humidity in the same rooms. Peixoto et al. found their recommendations for both largely unmet.
- Occupancy or the class timetable, so a CO2 curve can be matched to the load that produced it.
- Particles and VOCs where cleaning products or equipment are a concern. Peixoto et al. report average PM10 of 55.3 micrograms per m3 (threshold 50) and TVOC 1.6 to 8.9 times its 0.6 mg/m3 threshold when occupied, and name cleaning products and occupant movement as likely sources.
Sensors drift. In LBNL report 3279E (Fisk et al., 2010), 40% of 208 single-location CO2 sensors in 34 commercial buildings were off by more than 75 ppm at 1,010 ppm, and no facility manager said they had calibrated sensors since installation.
A class day gives a simple test (reasoning, not a finding): CO2 should rise when a class starts, level off and fall afterward, and a studio that keeps climbing through the whole class is the one to look at first. Where to place CO2 sensors for ventilation control, demand-controlled ventilation and how to read ventilation data in five minutes cover placement, control and the curves.
Nomestic measures indoor climate room by room (CO2, temperature, humidity and more). It works with or without a building management system (BMS), and nothing in the existing HVAC gets replaced. The devices are wireless and battery-powered, so a room takes minutes to equip.