Net zero buildings still need clean air: how to do both

Tight, low-energy buildings only get fresh air from their ventilation system. What the EPBD says, what field studies measured, and how to cut energy without cutting air.

A sealed building outline with a heat recovery unit and a CO2 gauge inside it

Net zero buildings still need clean air, because a building that leaks very little no longer ventilates by accident. The air a room receives has to be supplied on purpose, by a ventilation system that someone sizes, commissions and checks. Done well, that costs little energy. Done badly, the air delivered falls short, as the Austrian measurements below show.

Why net zero buildings depend on their ventilation system

A Passive House Institute page last updated in 2006 states that a continuous exchange of sufficient air has to be provided even in the cold season in any new building, and that this will only work using a mechanical system. Its reasoning is that wind- and temperature-driven ventilation fluctuates very significantly in the Central European climate and causes unacceptable drafts at high wind speeds. The same page says available heat exchangers reach a 75 to 95% recovery rate, and that with heat recovery the remaining ventilation losses are 2 to 7 kWh per m2 and year, against 20 to 30 kWh per m2 and year for dwellings in Central Europe without it.

What the EPBD says about indoor air quality in zero-emission buildings

The closest EPBD concept to net zero is the zero-emission building. Article 2(2) of Directive (EU) 2024/1275 defines it as a building with very high energy performance, zero or a very low amount of energy needed, zero on-site carbon emissions from fossil fuels and zero or a very low amount of operational greenhouse gas emissions. Article 11(3) sets the maximum energy demand threshold for a zero-emission building at least 10% lower than the Member State's nearly zero-energy threshold for total primary energy use on 28 May 2024. Article 7(1) requires zero-emission buildings from 1 January 2028 for new buildings owned by public bodies and from 1 January 2030 for all new buildings.

Air quality is written into the same directive. Article 13(5) requires Member States to have non-residential zero-emission buildings equipped with measuring and control devices for the monitoring and regulation of indoor air quality. For existing non-residential buildings, such devices are required, where technically and economically feasible, when the building undergoes a major renovation. A Commission guidance package of 30 June 2025, as summarized by REHVA, lists ventilation rate, CO2, PM2.5, formaldehyde, nitrogen dioxide, radon and carbon monoxide in its table of indoor air quality parameters. The wider rules are in EPBD indoor environmental quality monitoring: what the May 2026 date means.

What measured low-energy buildings show

Wallner et al. (2015, International Journal of Environmental Research and Public Health) compared 62 highly energy-efficient new homes with mechanical ventilation and 61 conventional new homes with window ventilation, all built 2010 to 2012 in Austria, mainly Vienna and Lower Austria. About 70% were detached houses and about 30% apartments. Measurements were taken about 3 months after move-in and again about a year later. In bedrooms, the median of the maximum hourly average CO2 was 1,360 ppm in the mechanically ventilated homes and 1,830 ppm in the others at the first visit, and 1,280 and 1,740 ppm at the follow-up. Median TVOC was 300 against 560 µg/m3 at the first visit. The authors write that the study does not support the hypothesis that occupants of mechanically ventilated low-energy houses are exposed to lower indoor air quality.

The same study shows the limit of that result. Only 11% of the bedrooms in the mechanically ventilated homes met the recommended supply air of 20 to 25 m3 per person and hour at the first visit, and 21% at the follow-up. Supply air was not measured in the comparison group. The authors put the shortfall down most likely to the outdated 2006 version of the Austrian standard H 6038, and write that the mechanical systems brought a significant improvement but could not be regarded as sufficient as the sole measure. They also report that for organizational reasons measurement intervals were often short or only spot samples were possible, and that nothing was measured from June to September.

A second study looked at how the answer depends on what is measured. Rueda López et al. (41st AIVC/ASHRAE IAQ conference, Athens, May 2022) logged CO2 every minute for three years in two occupied nearly zero energy houses in France (the COMEPOS project) and calculated 10 CO2-based indicators. Depending on the indicator, the indoor air quality was classified differently (good or poor) in the two houses. In the bedrooms, average CO2 differed by 20 to 34% between the two houses and cumulative exposure above 1,000 ppm by 28 to 70% (preliminary results). Two houses are a small sample, so the result says little about how common such differences are. Both studies measured homes, so their CO2 values do not transfer directly to offices.

Cutting energy without cutting air

Heat recovery lowers the heat lost with each cubic meter of outdoor air, and the Passive House figures above show the size of that effect for dwellings. Ameen et al. (a literature review in Energy and Buildings, vol. 351, 2026) report in their abstract that heat recovery ventilators reduce HVAC energy by 13.5 to 19.7% in cold climates, and that mechanical ventilation has been shown to increase energy use by about 20% in some cases. The abstract does not give the conditions of the underlying studies.

Demand control reduces airflow when rooms are not full. REHVA's guidance on commissioning demand-controlled ventilation (REHVA Journal, 02/2015) says a demand-controlled system will typically have airflow rates between 30 and 80% of the maximum airflow rate, depending on dimensioning and the minimal ventilation rate. In NREL's ComStock model of the US commercial building stock (report NREL/TP-5500-86897, January 2024, 2018 baseline), demand control cut total site energy by 2.6%. Some models show heating or cooling penalties, and NREL notes the cooling penalties mostly occur in models without economizers. That is a modeled result for the US stock, and the measure leaves out systems with an energy recovery ventilator, following ASHRAE 90.1. As general reasoning, not a published finding, savings from heat recovery and demand control do not simply add up when both are fitted, because heat recovery already makes each cubic meter cheaper. The control side is covered in Demand-controlled ventilation for commercial buildings.

Monitoring that shows both sides

Energy meters show whether the energy target is met. Measurements in the rooms show whether the air is adequate. Article 13(10)(d) of the EPBD lists monitoring of indoor environmental quality among the functions building automation and control systems must be capable of by 29 May 2026, and Article 13(9) requires such systems where technically and economically feasible, so national law decides which buildings are covered. REHVA's commissioning guidance includes a check that CO2 sensors give the same ppm reading in an empty building during the evening or night, and says a system should be tuned for both summer and winter and reviewed after a period of normal operation, for example one year.

A practical suggestion, not a published finding: in net zero buildings, start monitoring in the rooms with the highest occupant density, and track more than one CO2 measure (average, peak and time above a limit), since the French study shows how much the choice matters. Sensor placement is covered in Where to place CO2 sensors for ventilation control.

Nomestic measures indoor climate room by room, including CO2, temperature and humidity, and works with or without a building management system (BMS). Nothing in the existing HVAC gets replaced, and operators can override automatic adjustments at any time.