Is your ventilation ready for summer overheating?
Outdoor air cools a room only while it is cooler than the room. What CIBSE TM52, TM59 and EN 16798-1 cover, how night cooling behaves, and what to check before the first hot week.
Summer overheating in an office or school depends partly on ventilation, because outdoor air cools a room only while it is cooler than the indoor air and adds heat when it is not. Guidance for judging overheating exists, and each document has a stated scope. A check of the HVAC system before the first hot week should cover the outdoor-air controls, the night schedule and the room temperature data.
Temperature is the second-largest source of dissatisfaction in the Center for the Built Environment's office survey database, at 39% of respondents (sound privacy is first at 54%; Graham and colleagues, 2021).
What the guidance counts as overheating
CIBSE Technical Memorandum 52 (TM52, October 2013) is titled The limits of thermal comfort: avoiding overheating in European buildings. CIBSE's description centers on naturally ventilated buildings and includes a section on mechanically cooled buildings. A simulation software manual and a March 2025 overheating report for a London planning application describe its test: a room is classed as overheating if it fails two of three criteria. First, operative temperature at least 1 K above the maximum acceptable temperature for more than 3% of occupied hours between 1 May and 30 September. Second, a daily weighted exceedance above 6. Third, operative temperature more than 4 K above the maximum acceptable temperature. These criteria come from those two secondary descriptions, not from TM52 itself.
CIBSE TM59 is a residential document. Its 2017 edition covers dwellings, care homes and student residences (CIBSE). A 2026 edition, listed on CIBSE's site and reported by HBD in July 2026, extends the list to sheltered housing, hotels, hospital bedrooms and prisons. Neither list names offices or classrooms.
EN 16798-1:2019 gives design temperatures for sedentary work by category. The summer operative temperature ranges below come from a REHVA Journal article by Bjarne Olesen (06/2024), with the predicted percentage dissatisfied (PPD) for each category, and assume clothing of 0.5 clo and 1.2 met. An AIVC workshop presentation by Olesen (2023) gives the same ranges for offices, and a REHVA Journal article by Atze Boerstra (2019) gives categories I to III.
These are operative temperatures, which combine air temperature and mean radiant temperature. The ASHRAE thermal comfort vocabulary describes operative temperature as what people actually sense. A room sensor normally reports air temperature, so a sun-warmed west-facing room can feel warmer than its sensor says. That is general reasoning, not a finding from a source.
For buildings without mechanical cooling, EN 16798-1 allows an adaptive model in which the limits move with a running mean of the outdoor temperature. Olesen's REHVA article restricts it to mostly sedentary activity, operable windows and freedom to adapt clothing, and says it may not apply to open-plan offices where occupants have little window access. In the two English offices monitored by Gupta and Howard at Oxford Brookes University (2020), the naturally ventilated office exceeded 26°C for 15% of working hours in the non-heating season, against 1% in the mechanically ventilated one. Comfort as a whole in the BUS survey did not differ significantly, but occupants of the mechanically ventilated office rated summer conditions as significantly more satisfactory.
When outdoor air cools a room
A US national laboratory's building re-tuning training material (PNNL-SA-85063, 2012) gives the rule for outdoor-air cooling: use outdoor air as long as it is cooler than the return air, and in humid climates when it is about 5 to 10°F (roughly 3 to 6 K) below the return-air temperature. It also says not to use outdoor air during preheating or unoccupied fan operation.
The same material's checks for an economizer, the damper arrangement that brings in outdoor air for cooling, include confirming that the damper is wide open before mechanical cooling starts. With the damper wide open, mixed-air temperature should be within about 4 to 5°F (roughly 2 to 3 K) of outdoor air, allowing for supply-fan heat. A larger gap points to an actuator, linkage or seal problem. A damper stuck closed gives up outdoor-air cooling when the outdoor temperature suits it.
Outdoor air also carries heat and moisture into a room. The US Department of Energy federal technology alert DOE/EE-0293 (March 2004) on CO2-based demand control says warm, humid climates offer the most potential to save cooling energy from demand-controlled ventilation, because humidity reduces economizer opportunities. It also says that in dry climates, demand control without economizer cooling may even cause an energy penalty.
What night cooling can do
Night ventilation can pull heat out of a building's structure, within limits. A December 1996 article by Brian Webb (BRE) and Peter Concannon (Oscar Faber Applied Research) in Building Services Journal modeled a 6 m by 10 m by 3 m office with exposed heavyweight concrete ceilings, windows covering 40% of the external wall and internal gains of 20 to 30 W/m², using CIBSE example weather years for Kew and Heathrow. Night ventilation lowered daytime dry resultant temperature by up to 4°C at the start of occupation. In a four-week summer 1995 field test in a four-storey refurbished office, the dry resultant temperature on a floor with night ventilators open was 3°C lower than on the third floor, which had no night cooling, when the night air was 15°C, and the difference halved at 19°C. The article says the temperature reduction decreases as the ventilation rate rises beyond about 5 air changes per hour.
The same article warns about overcooling. Without control, the modeled office was below 18°C during occupied hours about 21% of the time with Kew weather and 17% with Heathrow weather. The authors recommend limiting ventilation in high daytime winds, preventing overcooling overnight, and cutting ventilation to background levels when outside air is warmer than inside during the day. They also name weather, security, noise and pollution as issues to deal with.
A 2006 paper by Nick Barnard of FaberMaunsell, presented to the Institute of Refrigeration, describes night ventilation at Stevenage Borough Council in England, where the fans run when the previous day exceeded 24°C and night ventilation is held off when the internal temperature falls to 18°C. It says night cooling is most effective where night temperatures fall below normal daytime comfort temperatures, as in the UK, and that hotter summers may need some mechanical refrigeration. Both sources describe UK conditions, from 1996 and 2006. The temperature drops depend on night air temperature, exposed thermal mass and control limits in those cases and cannot be carried over to another building.
What to check before the first hot week
The list below is a practical suggestion, except where a source is named above.
- Outdoor-air dampers and economizers: command each damper through its range and compare mixed-air, outdoor and return-air temperatures, as in the re-tuning checks above.
- Night schedules and limits: confirm the start condition and the stop temperature that prevents overcooling. The Stevenage settings of 24°C and 18°C are an example from one project.
- Room temperature sensors: compare each one with a reference thermometer, and look for rooms that read far from their neighbors.
- Last summer's data: list the rooms with the most occupied hours above the upper limit of the category the building was designed to. Those rooms come first.
- Cooling equipment: confirm that chillers, coils and fans start and reach their setpoints before the first warm days.
- Overrides: write down who may override the automatic settings during a heat wave, and how it is logged.
Finding the cause of a single room that runs hot is covered in too warm, too stuffy: how to find the cause room by room. Changes that need no new plant are in improving ventilation without replacing your HVAC.