What energy consultants should ask about ventilation in an audit

A basic energy audit reads ventilation from utility bills and a brief survey. Questions on measured airflow, schedules, controls, filters, heat recovery and CO2 data, tied to EN 16247 and the ASHRAE audit levels.

A checklist beside an air duct with an airflow arrow and a question mark

A basic energy audit reaches the ventilation system through utility bills and a brief survey of the building. Neither shows how much air a room gets at 3 p.m. on a Tuesday. The questions below are aimed at that gap. The audit standards describe how an audit runs and how deep it goes, and the parts of them that are publicly available do not list ventilation questions, so the list is practical judgment.

What EN 16247 and the ASHRAE levels define for an energy audit

EN 16247-1:2022 sets the general requirements for energy audits. Its scope says it specifies 'the requirements, common methodology and deliverables for energy audits' and applies to all forms of organizations and energy uses. CEN approved it on 3 July 2022 and it replaces the 2012 edition. EN 16247-2:2022 covers buildings: its scope is 'specific energy audit requirements in buildings', and it supersedes the 2014 edition. Only the first entries of the 2022 contents list are public (quality requirements, then the elements of the audit process, starting with preliminary contact). The 2014 edition's contents listed the steps as preliminary contact, start-up meeting, collecting data, field work, analysis, report and final meeting, and heating, cooling and ventilation were not separate headings. A TÜV NORD CERT service description for EN 16247-1 groups the work into seven phases and names no audit levels.

Depth comes from the ASHRAE audit levels. A 2013 presentation by the National Renewable Energy Laboratory for the US Department of Energy (a webinar called 'Energy Assessments') lists 'ASHRAE audit level definitions'. Level 1 is a walk-through analysis with utility bill analysis and a brief survey of the building. Level 2, the energy survey and analysis, adds a more detailed survey, a breakdown of energy use, a discussion of operation and maintenance impacts and a flag for where more detailed data collection and analysis are needed. Level 3, the detailed analysis of capital-intensive modifications, adds more detailed field data gathering and engineering analysis, including sub-metering, and detailed energy modeling. ASHRAE Standard 211-2018 (reaffirmed 2023), Standard for Commercial Building Energy Audits, defines the procedures for all three levels and the minimum reporting. The 2013 presentation predates it, and ASHRAE's public pages do not say what the standard requires for ventilation at each level; that is in the standard's text, which ASHRAE sells.

General reasoning: at Level 1 ventilation shows up as equipment seen on a walk-through and as a share of the bills. A question that needs hourly operating data fits a Level 2 scope, or a data request sent before the site visit.

Design airflow versus measured airflow

Start with what each air handler and zone delivers, and who measured it. A 2012 literature review by Pacific Northwest National Laboratory (PNNL-21281) says constant minimum airflow set points based on rules of thumb are still common in the field. It reports that integrators and installers often set the minimum to between 30 and 50% of a terminal box's maximum airflow, and that on pressure-dependent boxes the damper position cannot be relied on to deliver the required airflow. PNNL's Re-tuning Measure Guide (PNNL-SA-183964, April 2023) advises limiting minimum airflow to 10 to 15% of each VAV box's maximum.

Outdoor air needs the same questions: what minimum setting is in use, what occupancy it assumed and whether anyone measured the result. The guide notes that many operational sequences are based on unrealistic design occupancy and says to determine rough compliance with ASHRAE 62.1 and reduce any excess default ventilation rates. A PNNL chapter on economizers (PNNL-SA-85063, 2012) asks whether the minimum outdoor air position is 20% or less and says a higher value could be part of the problem with excess outdoor air and the energy needed to temper it.

The question cuts both ways. The US Department of Energy's federal technology alert on CO2-based demand-controlled ventilation (DOE/EE-0293, with field data from the early 2000s) quotes a controls company owner who warned that installing demand control might raise energy use in a chronically under-ventilated building. An energy audit that looks only for savings can recommend taking away air the building needs.

Schedules and control sequences

Ask which equipment is enabled by which schedule and compare it with the hours the building is used. The PNNL guide states that dedicated outdoor air systems and exhaust systems should not be enabled after hours or during start-up before occupancy, and it lists a separate measure for closing minimum outdoor air dampers at night, on weekends and during start-up. A PNNL re-tuning training chapter for small and medium-sized commercial buildings (PNNL-SA-92685, 2013) says exhaust fans with time clocks should be programmed to run only when needed, that fans without them can be given time clocks, and that the payback of such measures is in most cases less than 1 to 2 years. The same chapter suggests a 'Fan-On' setting while the thermostat is in occupied mode and says an 'Auto' fan setting may not meet ventilation code requirements, so the schedule question has a lower limit as well.

Then ask for the control sequence in writing and whether anyone has compared it with the trend logs. Meter data need to be hourly or 15-minute to show when equipment runs. The same chapter says monthly billing data does not show the time of use of an end use.

If the building has CO2-based demand control, ask when the sensors were last checked. In a Lawrence Berkeley National Laboratory (LBNL) study of 208 CO2 sensors in 34 commercial buildings, 40% were off by more than 75 ppm at about 1,010 ppm and 13% were off by more than 300 ppm. A REHVA Journal article on commissioning demand-controlled ventilation suggests checking that all CO2 sensors give the same reading when the building is empty.

Filters

Filters add fan energy. Eurovent Recommendation 4/24 (2023, update 1 published May 2024) estimates a filter's energy from its average pressure drop over its life, the operating hours and the fan efficiency, and it uses defaults of 6,000 hours a year and a fan efficiency of 0.5 when the real values are unknown. Pressure drop rises as the filter loads with dust. The practical questions are what final pressure drop triggers a change, whether it is logged and whether the fan has speed control. The document states that a lower pressure drop saves energy only with a speed-adjustable fan holding airflow constant; otherwise the airflow rises. It calls its result a rough estimation and notes that the laboratory test conditions behind the filter data may differ significantly from the individual application.

Heat recovery

Ask whether each air handler recovers heat from the exhaust air, which type it is and whether it is locked out when outdoor air can do the cooling. The PNNL guide says to aim to lock out heat recovery when it is appropriate to economize. For bidirectional non-residential ventilation units, Commission Regulation (EU) No 1253/2014 (Article 3 and Annex III) sets a minimum heat recovery thermal efficiency of 67% from 1 January 2016 and 73% from 1 January 2018 for systems other than run-around systems, and 63% and 68% for run-around systems. The regulation covers the placing on the market or putting into service of units, so each existing unit needs its own answer. A revision of the regulation was in draft in 2025 (Eurovent comments dated 20 May 2025), so the current figures should be checked. The heat recovery answer also changes any demand control estimate: the DOE alert says demand-controlled ventilation may not reduce energy use in buildings with heat exchangers.

CO2 data as a check on the answers

Room-level CO2 trends test the answers above against what the building does. The DOE alert suggests comparing sensor readings with outdoor air during an unoccupied period, which also checks the sensors. Reading the trend is interpretation. CO2 at outdoor level overnight while the fans run can point to outside air going to empty rooms (three signs your ventilation runs when nobody is there), and CO2 that keeps climbing during occupied hours can point to too little air for that room. Equipment-level checks are in where ventilation wastes energy, and the savings logic for demand control is in demand-controlled ventilation for commercial buildings.